Reset To Default Values - Samson 3730-6 Mounting And Operating Instructions

3730 series electropneumatic positioner with hart communication and pressure sensors
Table of Contents

Advertisement

7.9

Reset to default values

A reset allows the positioner to be reset to
the default settings. To reset the positioner,
the options Diag, Std and DS are available
in Code 36. Table 8 lists the reset functions.
Note: Code 36 – DS is usually selected
when the valve is mounted in another posi-
tion or when the positioner is to be mounted
to another valve.
Performing a reset does not necessarily
mean the positioner must be re-initialized.
Enable configuration:
® Code 3, display: No
Turn
Press
, Code 3 blinks
® YES
Turn
Press
, display
Reset start-up parameters:
Turn
® Code 36, display: – – –
Press
, Code 36 blinks
® DIAG/STD/DS
Turn
Press
. The parameters are reset depend-
ing on the option selected. Refer to Table 9.
Reset
Default No
Start-up – Settings
71
EB 8384-6 EN