Samson Series 3730 Mounting And Operating Instructions page 18

Type 3730-6 electropneumatic positioner
Table of Contents

Advertisement

Design and principle of operation
External position sensor
Travel
Cable
Permissible ambient
temperature
Immunity to vibration
Degree of protection
Binary input · Electrical isolation · Switching behavior configured over software
Active switching behavior (default setting)
Connection
Electric data
Contact
Closed,
R < 20 Ω
Open,
R > 400 Ω
Passive switching behavior
Connection
Electric data
Voltage
>6 V
<1 V
18
Same as positioner
10 m · Flexible and durable · With M12x1 connector · Flame-retardant acc. to
VDE 0472 · Resistant to oils, lubricants and coolants as well as other aggressive media
–40 to +90 °C with a fixed connection between positioner and position sensor
The limits in the test certificate additionally apply for explosion-protected versions.
Up to 10 g in the range of 10 to 2000 Hz
IP 67
For external switch (floating contact) or relay contact
Open-circuit voltage when contact is open: max. 10 V
Pulsed DC current reaching peak value of 100 mA and RMS value of 0.01 mA when
contact is closed
ON switching state (default setting)
OFF switching state (default setting)
For externally applied DC voltage, reverse polarity protection
3 to 30 V DC · Static destruction limit 40 V · Current consumption 3.7 mA at 24 V
ON switching state (default setting)
OFF switching state (default setting)
EB 8384-6 EN

Advertisement

Table of Contents
loading

Table of Contents