4. Place the lever (1) and disk spring (1.2)
on the sensor shaft. Place the lever in
mid-position and hold it in place. Screw
on the nut (1.1).
5. Place follower clamp (3) on the actuator
stem, align it and screw tight so that the
mounting screw is located in the groove
of the actuator stem.
6. Place the mounting plate together with
the sensor onto the actuator yoke so that
the follower pin (2) rests on the top of the
follower clamp (3). It must rest on it with
spring force. Fasten the mounting plate
(21) onto the actuator yoke using both
fixing screws.
7. Mount cover (11) on the other side.
Make sure that the vent plug is located at
the bottom when the control valve is in-
20
21
1.1, 1.2
2
Fig. 16: Mounting according to IEC 60534-6 (NAMUR)
EB 8384-6 EN
Attachment to the control valve – Mounting parts and accessories
14.1
3 14
9.1
stalled to allow any condensed water
that collects to drain off.
4.7.2
Mounting the position
sensor with attachment
according to
IEC 60534-6
− Required mounting parts and accesso-
ries: Table 7 on page 57
Fig. 16
1. Place the lever (1) on the position sensor
in mid-position and hold it in place. Un-
thread the nut (1.1) and remove the lever
together with the disk spring (1.2) from
the sensor shaft.
9
1
Lever
1.1
Nut
1.2
Disk spring
2
Follower pin
3
Follower plate
9
Coupling
9.1
Bracket
14
Bolt
14.1
Screw
20
Position sensor
21
Bracket
45