Units
Terminal Connections
1, 2, 3...
C200HW-PA204: AC Input
1. AC Input
2.
Voltage selector
terminals
3. LG
4. GR
C200HW-PA204R: AC Input
1. AC Input
2.
Voltage selector
terminals
3. LG
4. GR
7. RUN output
1. AC Input (C200HW-PA20jj Only)
Supply either 100 to 120 VAC or 200 to 240 VAC to the AC input terminals. If
one power supply phase of the equipment is grounded, connect the
grounded phase side to the L
2. Voltage Selector Terminals (C200HW-PA20jj Only)
Short these terminals with a metal short bar when 100 to 120 VAC is being
supplied to the AC input terminals.
3. LG
Ground the LG terminal to 100 Ω or less to increase resistance to noise and
protect against possible electrical shock.
C200HW-PA204S: AC Input
L
/N
2
100 to 120 VAC/
1. AC Input
200 to 240 VAC
Input
L
1
2.
Voltage selector
100 to 120
Close
terminals
200 to 240
Open
3. LG
4. GR
5. 24 VDC output
C200HW-PA209R: DC Input
L
/N
2
100 to 120 VAC/
1. AC Input
200 to 240 VAC
Input
L
1
100 to 120
2.
Voltage selector
Close
terminals
200 to 240
Open
3. LG
4. GR
RUN OUTPUT
250 VAC
7. RUN output
24 VDC
2 A
C200HW-PD024: DC Input
6. DC Input
24 VDC
3. LG
4. GR
/N (or L
/N if so indicated) terminal.
2
1
Section 2-2
L
/N
2
100 to 120 VAC/
200 to 240 VAC
Input
L
1
100 to 120
Close
200 to 240
Open
24 VDC 0.8 A
Output
L
/N
2
100 to 120 VAC/
200 to 240 VAC
Input
L
1
100 to 120
Close
200 to 240
Open
RUN OUTPUT
240 VAC
24 VDC
2 A Resistive
21