Omron C200HE-CPU11 Installation Manual page 178

Hide thumbs Also See for C200HE-CPU11:
Table of Contents

Advertisement

Specifications
Transistor Output Unit C200H-OD21B (32 Points)
(Load Short-circuit Protection Provided)
Note When the short-circuit/overload protection is activated for a contact point, the output for that point is turned
OFF. At the same time, lamp "F" lights up, and the alarm from AR0205 to AR0214 corresponding to the I/O
number turns ON. After the cause of the error has been removed, the alarm will be cleared automatically
when the internal temperature of the element drops.
Circuit Configuration
166
Max. Switching Current
Min. Switching Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuses
Power for External Supply
Weight
Alarm Indicator
Load Short-circuit Prevention
(see note 1)
Dimensions
Output LED
indicator
Alarm
LED
indi-
cator
Output LED
indicator
+10%
0.5 A 24 VDC
/
(5 A/Unit)
–15%
None
0.1 mA max.
0.8 V max.
0.1 ms max.
0.3 ms max.
32 (32 points/common)
180 mA 5 VDC max.
One 7 A fuse (1 fuse/common)
The fuses are not user-replacable.
+10%
160 mA 24 VDC
/
–15%
(5 mA × number of ON pts)
180 g max.
Lamp F lights (unless fuse is broken).
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance.
C-shape
to
0 V
to
0 V
to
0 V
to
0 V
Appendix B