Specifications
6. When wiring output circuits, be sure to use the correct polarity for the external power supplies. Wiring
with incorrect polarity may result in erroneous operation of the load.
High-density I/O Unit Limitations
Limitations on the switching capacity of C200H-OD215/MD115/MD215 Transistor Output Units and the usable
number of I/O points in the C200H-ID215 and C200H-MD215 are shown below.
Switching Capacity
The switching capacity of C200H-OD215/MD115/MD215 Transistor Output Units depends on the power supply
voltage, as shown below.
TTL I/O Unit C200H-MD501
(Used as I/O Unit with 16 Inputs and 16 Outputs)
Output Specifications
(Connector 1)
Input Specifications
(Connector 2)
100
50
16
0
0
4.5
10
Power Supply Voltage (V)
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Fuses
Power for External Supply
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
High-speed Inputs
20.4
26.4
5 VDC 35 mA (280 mA/common, 560 mA/Unit;
output resistance 4.7 kW)
None
0.1 mA max.
0.4 V max.
0.2 ms max.
0.3 ms max.
2 (8 points/common)
2 (1 fuse/common; fuses are not user-replacable.)
20 mA 5 VDC min. (1.2 mA × no. of outputs ON)
5 VDC
4.5 to 5.5 VDC
1.1 kW
3.5 mA (at 5 VDC)
3.0 VDC min.
1.0 VDC max.
2.5 ms/15 ms max. (switchable)
2.5 ms/15 ms max. (switchable)
2 (8 points/common)
8 points (connector 2 terminals 8 to 15, when set)
Pulse width: 1 ms/4 ms min. (switchable)