Specifications
C200H-OD21A Transistor Output Unit (16 Points, Sourcing)
(Load Circuit Protection Provided)
Circuit Configuration
Note When short-circuit/overload protection is activated, all 16 outputs will be switched OFF and the ALARM
output becomes active (low level). The problem can be detected externally by connecting a DC Input Unit to
the ALARM output or by connecting an alarm output indicator. It's not possible to connect both the Input Unit
and the indicator at the same time. Unless the external I/O power supply is connected and turned ON, the
indicator will not light even if the output contact turns ON.
146
Max. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Load Short-circuit Protection
Power for External Supply
Weight
Alarm Output (See note 1.)
Reset Input
Load Short-circuit Protection
Dimensions
Output
indicator
2 kΩ
+10%
24 VDC
/
, 1.0 A (4 A/Unit)
–15%
0.1 mA max.
0.8 V max.
0.1 ms max.
0.3 ms max.
1 (16 points/common)
160 mA 5 VDC max.
Detection current: 1.2 A min (1.6 A typical)
+10%
35 mA 24 VDC
/
min.
–15%
400 g max.
No. of outputs: 1 (2 kΩ internal resistor)
Connectable Units: Only the following DC Input
Units can be connected:
C200H-ID001, ID211, ID212, IM211 (DC), IM212
(DC), ID215, ID501, MD115, MD215, MD501
Used when alarm output turns ON. Value will
depend on the external power supply. (See note 2.)
Detection current: 1.2 A min.
(1.6 A typical)
B-shape
to
0 V
Appendix B