Preparing for Installation
System Example
Vitotronic 200 (set codes at every Vitotronic 200 - boiler control)
Switching mode from standalone/weather compensated control to constant temperature control (see page 14).
Required coding
Group
Code
General
01:2
General
07:1
07:2
07:3
07:4
07:...
Vitotronic 300-K
Required coding
Group
Code
General
00:...
General
7E:0
Cascade
35:1
35:2
35:3
35:4
35:...
Vitotronic 200-H (if installed)
Required coding
Group
Code
General
97:1

Installation Information for the Vitotronic 200

If a DHW tank is to be integrated into the system, make
the connection at the Vitotronic 300-K (or if installed,
at the Vitotronic 200-H).

Installing a Cascade Communication Module - Vitodens 200-W

8
(continued)
Multi boiler system with Vitotronic 300-K
Note: Code "00:0" is set automatically.
Setting the boiler number at the Vitotronic 200 of the respective boiler
Boiler 1 (factory set condition)
Boiler 2
Boiler 3
Boiler 4
... Boiler (up to 8)
System version, see table for coding address 00 in the overview on page 73.
Without positive pressure flue gas cascade
Do not adjust
Multi boiler system with two boilers
Multi boiler system with three boilers
Multi boiler system with four boilers (factory set condition)
Multi boiler system with ... boilers (up to 8)
The outside temperature is accepted by the LON BUS
Vitotronic 200, HO1B and 300-K, MW2C Installation/Service
For installation, commissioning, maintenance
and service of Vitodens 200-W or Vitocrossal
300 CU3A with Vitotronic 200: see the
appropriate installation instructions and service
instructions.
Depending on the package ordered the KMK
communication module may be part of the standard
delivery.
Optional LON communication is available using the LON
communication module. LON communication will require
LON communication cards for the Vitotronic 300-K and
one card for each boiler installed in the system.