Calling Up Coding Level 2; General" Group - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Digital boiler control unit
Table of Contents

Advertisement

Vitotronic 200, HO1B and 300-K, MW2C Installation/Service

Calling up Coding Level 2

"General" Group

Select "General"
Coding
Coding in the factory setting
00:0
11:≠ 9
2A:0
2D:0
--
No access to the coding addresses
for the combustion controller coding
Without wireless outdoor temperature
sensor
Do not adjust!
Prior to coding the Vitotronic 200, ensure the boiler is
in cascade mode. See below.
For the Vitotronic 200, see boiler Service
Instructions
1. Press
and OK for approximately 4 seconds.
2. Use
to scroll to serviceand select with OK.
3. Use
to scroll to service functionsand select
with OK.
4. Use
to scroll to multi-boiler systemand select
with OK.
5. When complete to exit press
Note: At coding level 2, all codes are accessible,
including the codes at coding level 1.
Codes that have not been assigned due to the
heating system equipment level or the setting of
other codes are not displayed.
1. Press OK and
simultaneously for approximately
4 seconds.
2. Press OK and
simultaneously for approximately
4 seconds.
3. "Coding level 2"
4. Select group of required coding address:
- "General"
- "Boiler"
- "All codes standard device"
5. Select coding address.
6. Select value according to the following tables and
confirm with "OK".
7. If you want to reset all codes to their factory setting:
Select "Standard setting" in "Coding level 2".
Note: This also resets codes at coding level 1.
Possible change
00:1
Do Not Adjust
to
00:10
11:9
Access open to the coding
addresses for the combustion
controller coding.
2A:1
With wireless outdoor
temperature sensor (automatic
recognition).
2A:2
Wireless outdoor temperature
sensor not used.
--
Coding 2 Vitotronic 200
.
--