Boiler" Group - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Digital boiler control unit
Table of Contents

Advertisement

Vitotronic 200, HO1B and 300-K, MW2C Installation/Service

"Boiler" Group

(continued)
Coding
Coding in the factory setting
0D:0
0E:0
13:1
14:1
15:1
21:0
23:0
24:0
28:0
2E:0
2F:0
(only for Vitodens 200-W)
30:3
Vitodens 200-W only
30:1
Vitocrossal 300 CU3A
only
31:...
NOT USED
38:0
Do not adjust!
Do not adjust!
Do not adjust!
Do not adjust!
Do not adjust!
No service interval (hours run)
selected
No time interval for burner
service
No "Service" display
No burner interval ignition
Do not adjust!
Venting program/fill program
disabled
When changing from a single
boiler to a multiboiler operation,
the coding address may
automatically reset to 30:3. To
prevent continuous boiler pump
operation, adjust the coding
address for each boiler to 30:0.
When changing from a single
boiler to a multiboiler operation,
the coding address may
automatically reset to 30:1. To
activate boiler pump operation,
adjust the coding address for
each boiler to 30:0.
Set speed in % of the internal
circulation pump when operated
as boiler circuit pump, specified
by the boiler coding card
Status burner control unit:
Operational (no fault)
Possible change
--
--
--
--
--
21:1
Number of hours run before the
to
burner should be serviced is
21:100
adjustable from 100 to 10,000 h
One adjusting step ≙ 100 h.
23:1
Interval adjustable from 1 to 24
to
months.
23:24
24:1
"Service" display (the address is
automatically set and must be
manually reset after a service has
been carried out).
28:1
Interval adjustable from 1 hour
to
to 24 hours. The burner is force
28:24
started once every 30 seconds
(only when operating with LPG).
--
2F:1
Venting program enabled.
2F:2
Fill program enabled.
30:0
Coding address should be set
to 30:0, if not adjust to 30:0
31:0
Set speed adjustable from
to
0 to 100%.
31:100
38:≠0
Status burner control unit: Fault.
Coding 2 Vitotronic 200
--
--
--
--
--
--
71

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300-k

Table of Contents