General" Group; Boiler" Group - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Digital boiler control unit
Table of Contents

Advertisement

Coding 1 Vitotronic 200

"General" Group

Coding
Coding in the factory setting
System design (boiler connected to cascade)
00:0
Participant no.
77:1
LON participant
number
Lock out controls
8F:0
Operation in the
standard menu
and extended menu
enabled.
Note: The respective
Set supply temperature for external demand
9B:70
Set supply temperature
for external demand
158°F (70°C)

"Boiler" Group

Coding
Coding in the factory setting
Single/multi boiler system
01:2
Do Not Adjust
Boiler number
07:1
Boiler number in multi
boiler systems
Burner service in 100 hours
21:0
No service interval
(hours run) selected
Service interval in months
23:0
No time interval for
burner service
Service status
24:0
No "Service" display
Filling/Venting
2F:0
Venting (bleeding)
Vitodens
program/fill program
200-W only
disabled
66
Possible change
--
00:1
to
00:10
77:2
to
77:99
8F:1
8F:2
code is only
activated when
you exit the
service menu.
9B:0
to
9B:127
Possible change
--
07:2
to
07:8
21:1
to
21:100
23:1
to
23:24
24:1
2F:1
2F:2
Vitotronic 200, HO1B and 300-K, MW2C Installation/Service
Do Not Adjust
LON participant number, adjustable from 1 to 99:
1 - 8 = Boiler
9 = Cascade
10 - 96 = Vitotronic 200-H
97 = Vitogate 300
98 = Vitogate
99 = Vitocom
Operation in standard menu
and extended menu blocked.
Emissions test mode can be enabled.
Operation enabled in the standard menu and
blocked in the extended menu.
Emissions test mode can be enabled.
Set supply temperature for external demand
adjustable
from 32 to 260°F (0 to 127°C)
(limited by boiler-specific coding).
--
Boiler number 2 to 8 in multi-boiler systems.
Number of hours run before the burner should be
serviced is adjustable from 100 to 10,000 h
One adjusting step ≙ 100 h.
Interval adjustable from 1 to 24 months.
"Service" display (the address is automatically
set and must be manually reset after a service
has been carried out).
Venting (bleeding) program enabled.
Fill program enabled.