Fluke 434-II User Manual page 147

Three phase energy and power quality analyzer
Hide thumbs Also See for 434-II:
Table of Contents

Advertisement

Transient capture
Volts
cursor reading
rms reading
Minimum detect duration
Sampling rate
WIRING COMBINATIONS
1Ø + NEUTRAL
1Ø SPLIT PHASE
1Ø IT NO NEUTRAL
3Ø WYE
3Ø DELTA
3Ø IT
3Ø HIGH LEG
3Ø OPEN LEG
2-ELEMENT
2½-ELEMENT
INVERTER
EFFICIENCY
info@Fluke-Direct.ca
Measurement Range
Resolution
± 6000 Vpk
0.1 V
10 ... 1000 Vrms
0.1 V
5 µs
200 kS/s
Single phase with neutral
Split phase
Single phase system with two phase voltages without neutral
Three phase four wire system WYE
Three phase three wire system Delta
Three phase system without neutral WYE
Four wire three phase Delta system with center tapped high leg
Open delta three wire system with 2 transformer windings
Three phase three wire system without current sensor on phase L2 / B (2 watt
meter method)
Three phase four wire system without voltage sensor on phase L2 / B
dc voltage and current input with ac output power (automatically displayed and
selected in Inverter Efficiency mode)
Fluke-Direct
Specifications
Electrical Measurements
Accuracy
± 15% of cursor reading
± 2.5% of Vnominal
.ca
1.800.868.7495
27
27-9