6. 34. 8
<F719: Run command clear select>
■ Function
This parameter is used to select whether the run command is retained or cleared when the following
4
events occur during panel run or RS485 communication run.
• Coast stop with standby function (ST) is off (OFF display)
• Coast stop with coast command function (FRR) is on (OFF display)
4
• Coast stop with terminal [STO] is off ("PrA" display)
• Power circuit undervoltage (MOFF) alarm
6
■ Parameter setting
Title
F719
9
■ Difference between the settings
<F719> setting value
0
1
2
3
* If "PrA" alarm occurs when terminal [STO] is off, run command is cleared regardless of the <F719>
setting.
Retain run command.
Inverter restarts when coast stop is cleared after its occurrence.
Inverter restarts when power is supplied again when the power circuit undervoltage (MOFF) alarm
occurs.
6. [Advanced] How to use parameters

Clearing run command

Parameter name
Run command clear
select
Coast stop
Run command clear
F719 : Run command clear select
0: Clr at coast stop
1: Retain run command
2: Clr at coast stop & MOFF
3: Clr at coast stop, MOFF & Cmod
Adjustment range
0: Clear at coast stop. Retain when MOFF
occurs and CMOd is changed.
1: Retain run command.
2: Clear at coast stop and at MOFF. Retain
when CMOd is changed.
3: Clear at coast stop, at MOFF and when
CMOd is changed.
When power circuit
undervoltage (MOFF)
alarm occurred
Retain run command
Retain run command
Run command clear
Run command clear
6-172
E6582062
STOP
0.0Hz
14:14
Default setting
2
When <CMOd> is
changed
Retain run command