6. 20 Switching to commercial power run

<F354: Commercial power/Inverter switching>
<F355: Commercial power switching frequency>
<F356: Inverter switching wait time>
<F357: Commercial power switching wait time>
<F358: Commercial power switching frequency continu-
ous time>
■ Function
This function allows output of switching signals to an external sequence (such as MC) so that when
tripping occurs, operation will be switched to commercial power run without stopping the motor.
■ Parameter setting
Title
Parameter name
F354
Commercial power/
Inverter switching
F355
Commercial power
switching frequency
F356
Inverter switching wait
time
F357
Commercial power
switching wait time
F358
Commercial power
switching frequency
continuous time
*1
Depending on the setup menu. Refer to [5. 3. 10], [11. 10].
*2
Depending on capacity. For details, refer to [11. 5].
Trips that are automatically switched are those not displayed as "OCL", "E", "EF1", and "EF2".
<F341: Brake function> will not be enabled.
F354 : CP/ inverter seitch
0: Disabled
1: Switch at trip
2: Switch at F355
3: Switch at trip and at F355
Adjustment range
0: Disabled
1: Switch at trip
2: Switch at F355
3: Switch at trip and at F355
0 - UL
0.10 - 10.00
0.10 - 10.00
0.10 - 10.00
6-77
E6582062
STOP
0.0Hz
13:22
Unit
Default setting
0
Hz
*1
50.0/60.0
s
*2
s
0.62
s
2.00
6. [Advanced] How to use parameters
3
4
6
9