Example of 0 - 10 Vdc voltage input setting
Output frequency (Hz)
<F204>
(60Hz)
<F202>
(0Hz)
0V
<F201>
<F203>
0%
100%
Example of 4 - 20 mAdc current input setting
Output frequency (Hz)
<F219>
(60Hz)
<F217>
(0Hz)
4mA
<F216>
<F218>
0%

5) Setting the time elapsed before PID control starts

Waiting time until starting PID control system can be set to avoid PID control until the control
system becomes stable at power on.
The inverter ignores feedback input signals and runs at the frequency determined by the
frequency command value for the period of time set with <F369: PID1 start wait time>, and
enters PID control after the elapsed time.
Title
Parameter name
F369
PID control start wait time
Output frequency (Hz)
Terminal [RR] input value
10V
Terminal [II] input value
20mA
100%
Adjustment range
0 - 2400
5-59
Example of -10 - +10 Vdc voltage input setting
<F213>
(60Hz)
<F211>
(0Hz)
0V
10V
<F210>
<F212>
0%
100%
Unit
s
5. [Fundamental operation] How to use parameters
E6582062
Terminal [RX] input value
Default setting
0
3
4
5
9