Standard Connection Diagram - Sink, An Example Of A Standard Connection For 480 V Class, 200 To 280 Kw (Frame Size A8) - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

[Standard connection diagram - Sink]
This diagram shows an example of a standard connection for 480 V class, 200 to 280 kW (frame size A8).
Power supply
480 V class:
200 - 280 kW Three-phase 380 - 440 V-50 Hz
Three-phase 380 - 480 V-60 Hz
MCCB
480/240 V
transformer
MC
Optional control
power supply unit
*7
b-contact of
overload relay
ON
OFF
RUN
*1
Be sure to mount the DC reactor. It is not required for DC power input terminal. A circuit between the terminals [PA/+] and [PO] is not short circuited
(at the time of shipping).
*2
To input DC power, connect the inverter between the terminals [PA/+] and [PC/-]. It is not used in conjunction with the DC reactor option DCL1.
*3
When the inverter is used with a DC power supply, a circuit to suppress an inrush current is required. Please contact your Toshiba distributor for
information.
*4
When the inverter is used with a DC power supply, three-phase power input for cooling fan driving is required separately.
*5
When a braking resistor (optional) is mounted, a braking unit (optional) is also required.
*6
For the switch function, refer to [2. 3. 5].
*7
To supply control power from an external power supply for backing up the control power supplied from the inverter, an optional control power supply
unit (CPS002Z) is required. In this case, it is used in conjunction with the inverter internal power supply.
Set <F647: Control power option failure detection> to back up the control power supply.
For details, refer to [6. 30. 20].
*8
The reset signal is activated by ON→OFF trigger input.
*9
Connect to power to comply with OVC2 (Over Voltage Category 2). Isolation transformer is necessary when connecting to power supply (OVC3).
*2
+DC -DC
*3
*1
PO
PA/+
MC
R/L1
S/L2
EMC
filter
T/L3
Fan
*4
RO
SO
TO
RUN
+SU
CC
Control
*7
circuit
FLA
*9
FLB
Surge
absorber
PLC
FLC
RUN
SW1
R1A/R2A
*9
R1C/R2C
FM AM CC
Frequency
Ammeter
meter
Ammeter or voltmeter
(Or, input voltage signal of 0 - 10 V between the terminals [RR] and [CC])
2-31
Braking unit Braking resistor
PA
*5
*5
PB
PC/- BU+ BU-
U/T1
Power
V/T2
circuit
W/T3
DC/DC
F
R
RES
S1
S2
S3
S4
S5
CC
P24
SINK
SOURCE
FP
PLC
*6
STOA
STOB
RX
II
RR PP
Voltage signal: -10 to +10 V
Current signal :4(0) to 20 mA
External potentiometer
E6582062
Motor
M
Digital input
Fwd run
Rev run
*8
Reset 1
Preset speed switching 1
Default
Preset speed switching 2
setting
Preset speed switching 3
Preset speed switching 4
Preset speed switching 5
Common
Pulse counter
2. Installation and wiring