This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109010706ffff or 0x800109010706ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0494
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Replace power supply.
• 80010901-0707ffff : Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted. (Rear BP1 Temp)
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109010707ffff or 0x800109010707ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
364
HX3510-G, HX5510, HX5510-C, HX7510 Installation and Service Guide