Step 1-Install The Dvc6200 On The Valve - Fisher FIELDVUE DVC6200 Quick Start Manual

Digital valve controllers
Hide thumbs Also See for FIELDVUE DVC6200:
Table of Contents

Advertisement

DVC6200 Digital Valve Controllers
January 2017
Step 1—Install the DVC6200 on the Valve
Housing Variations
The DVC6200 housing is available in two different configurations, depending on the actuator mounting method.
Figure 1 shows the available configurations.
Figure 1. Housing Variations
HOUSING FOR LINEAR AND ROTARY
ACTUATORS, FISHER 657 SIZE 30i - 70i,
AND 667 SIZE 30i - 76i
LINEAR, M8
W9703
General Mounting Guidelines
If ordered as part of a control valve assembly, the factory will mount the digital valve controller on the actuator and
calibrate the instrument. If you purchased the digital valve controller separately, you will need a mounting kit. The
following procedures are general guidelines. See the instructions that come with the mounting kit for detailed
information on mounting the digital valve controller to a specific actuator model.
CAUTION
The magnet assembly material has been specifically chosen to provide a long‐term stable magnetic field.
However, as with any magnet, care must be taken when handling the magnet assembly. Another high powered magnet
placed in close proximity (less than 25 mm) can cause permanent damage. Potential sources of damaging equipment
include, but are not limited to: transformers, DC motors, stacking magnet assemblies.
General Guidelines for use of High Power Magnets with Positioners
Use of high power magnets in close proximity to any positioner which is operating a process should be avoided. Regardless
of the positioner model, high power magnets can affect the positioner's ability to control the valve.
4
INTEGRAL OUTPUT
PRESSURE PORT
ROTARY NAMUR, M6
HOUSING FOR
FISHER GX ACTUATORS
SLOTS FOR
W9704
MOUNTING BOLTS
Quick Start Guide
D103556X012
SIS
HOLE FOR
MOUNTING BOLT