FWS 27
FWS Solartronic
• Switch off the 230V connection of the fresh water station
• Turn all ball valves of the primary and secundary circle of the
station to the closed position.
• Screw the union nut directly below the ball valve for the cold
water connection of and take the strainer out.
• The strainer can be cleaned or replaced now.
• After fitting of the strainer tighten the screw now.
• Turn on now all ball valves slowly on. Begin with ball valve
on the cold water side (connection I). Vent the whole device
by opening and closing one hot water valve serval times
until no more air has been eliminated from the
instantaneous water heater and the fresh water station unit.
• Connect the 230V electrical line with the grid.
• Reconnect the voltage to the house fuse.