E2: Motor 1 Parameters; F4: Analog Monitor Card (Ao-A3) - YASKAWA P1000 Quick Start Manual

Hide thumbs Also See for P1000:
Table of Contents

Advertisement

E2: Motor 1 Parameters

u
No.
(Addr.
Name
Hex)
E2-01
Motor Rated Current
(30E)
E2-02
Motor Rated Slip
(30F)
E2-03
Motor No-Load Current
(310)
E2-04
Number of Motor Poles
(311)
E2-05
Motor Line-to-Line
(312)
Resistance
E2-06
Motor Leakage Inductance
(313)
E2-10
Motor Iron Loss for Torque
(317)
Compensation
E2-11
Motor Rated Power
(318)
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model 1. This value has two decimal places (0.01 A) if the drive is set
for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor capacity is
higher than 11 kW.

F4: Analog Monitor Card (AO-A3)

u
No.
(Addr.
Name
Hex)
F4-01
Terminal V1 Monitor
(391)
Selection
F4-02
(392)
Terminal V1 Monitor Gain
F4-03
Terminal V2 Monitor
(393)
Selection
F4-04
(394)
Terminal V2 Monitor Gain
F4-05
(395)
Terminal V1 Monitor Bias
F4-06
(396)
Terminal V2 Monitor Bias
F4-07
Terminal V1 Signal Level
(397)
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Sets the motor nameplate full load current in amps. Automatically set during
Auto-Tuning.
Sets the motor rated slip. Automatically set during Auto-Tuning.
Sets the no-load current for the motor. Automatically set during Auto-Tuning. Default:
Sets the number of motor poles. Automatically set during Auto-Tuning.
Sets the phase-to-phase motor resistance. Automatically set during
Auto-Tuning.
Sets the voltage drop due to motor leakage inductance as a percentage of motor
rated voltage. Automatically set during Auto-Tuning.
Sets the motor iron loss.
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set
during Auto-Tuning.
Sets the monitor signal for output from terminal V1. Set this parameter to the
last three digits of the desired Uo-oo monitor. Some U parameters are
available only in certain control modes.
Sets the gain for voltage output via terminal V1.
Sets the monitor signal for output from terminal V2. Set this parameter to the
last three digits of the desired Uo-oo monitor. Some U parameters are
available only in certain control modes.
Sets the gain for voltage output via terminal V2.
Sets the amount of bias added to the voltage output via terminal V1.
Sets the amount of bias added to the voltage output via terminal V2.
0: 0 to 10 V
1: -10 to 10 V
Description
Description
B.5 E: Motor Parameters
Values
Page
<1>
Default:
Min.: 10% of drive
rated current
106
Max.: 200% of
drive rated current
<2>
<1>
Default:
Min.: 0.00 Hz
Max.: 20.00 Hz
<1>
Min.: 0 A
<2>
Max.: E2-01
Default: 4
Min.: 2
Max.: 48
<1>
Default:
Min.: 0.000 Ω
Max.: 65.000 Ω
<1>
Default:
Min.: 0.0%
Max.: 40.0%
<1>
Default:
Min.: 0 W
Max.: 65535 W
<1>
Default:
Min.: 0.00 kW
Max.: 650.00 kW
Values
Page
Default: 102
Range: 000 to 999
Default: 100.0%
Min.: -999.9
Max.: 999.9
Default: 103
Range: 000 to 999
Default: 50.0%
Min.: -999.9
Max.: 999.9
Default: 0.0%
Min.: -999.9
Max.: 999.9
Default: 0.0%
Min.: -999.9
Max.: 999.9
Default: 0
Range: 0, 1
197