Settings\Hot Water - IVT Rego 5101 Installation Manual

Table of Contents

Advertisement

Settings
4.5

Settings\Hot water

Setting
Hot water
Hot water type
Temperatures
Tab. 36 Hot water
18
When the heat pump is to produce hot water:
B Enter how the heat pump is to control hot water production.
B Select Local sensor when there is a locally connected hot water cylinder with local sensor to
measure the hot water temperature.
B Select Previous HP when the heat pump receives values for the hot water temperature from
the previous heat pump.
B Select Communicated when the heat pump has all information about the hot water
temperature and start/stop limits via communicating (Modbus) control (
page 10).
Actual v.:
Start:
Stop:
Max temperature:
B Set start and stop values for hot water production.
The factory settings refer to heat pumps with Local sensor. In Previous HP 2 K lower
temperatures are recommended. In Communicated the values have no meaning.
Max temperature displays the calculated possible highest hot water temperature.
Factory
No hot water
Display
53 °C
57 °C
Display
Range
No hot water
Local sensor
Communicated
Previous HP
Not E21
Chapter 4.1,
6 720 645 172 (2010/07) en