IVT Rego 5101 Installation Manual page 16

Table of Contents

Advertisement

Settings
Setting
Additional heat
Additional heat type
Settings
Alarm delay
ECO-drive
Tab. 35 Modulated additional heat, Mixed additional heat
4.4.1
Internal add. heat
The internal additional heat has three steps, E2.E1 (4.5
kW), E2.E2 (4.5 kW) and E2.E3 (6.75 kW). When all
stages are connected a total of 15.75 kW is obtained. A
degree minute calculation is used to activate each stage.
E2.E1: The compressor is running and E11.T1 does not
reach its set point value. Calculation of difference
between E11.T1 set point value – set Hysteresis (3 K)
and E11.T1 actual value are added continuously. When
the sum reaches the value set in Delay (180 °min) stage
1 is activated.
16
B Set applicable Additional heat type and desired additional heat operation. In Modulated add.
heat and Mixed add. heat is shown:
Start E71
Hysteresis
Delay
Actual v.:
Stop E71
Delay
Actual v.:
PID E71
P:
I:
D:
T1, Sp, Out
B Set conditions for engaging/disengaging the additional heat.
B Set values for mixing valve control.
Actual and set point value for T1 is shown. In addition the output signal is shown in %.
Alarm delay
The function is only displayed at Mixed add. heat.
B Set with what time alarm External add. heat out of order is to be delayed (
page 33).
ECO-drive
Start
Stop after
B Indicate Yes if activation of the additional heat is to be delayed during a set time period.
The delay increases by 25%.
Factory
No additional heat
Comp. + add. heat
3 K
180 °min
Display, can be changed
10°min
Display, can be changed
1
100
0
Display
30 min
No
22:00
6 hr
E2.E2: Stage 1 is connected and E11.T1 does not reach
its set point value. Calculation of difference between
E11.T1 set point value – set Hysteresis (3 K) and E11.T1
actual value are added continuously. When the sum
reaches the value set in Delay (60 °min) stage 2 is
activated.
E2.E3: Stage 2 is connected and E11.T1 does not reach
its set point value. Calculation of difference between
E11.T1 set point value – set Hysteresis (3 K) and E11.T1
actual value are added continuously. When the sum
Range
No additional heat
Internal add. heat
District heating
Modulated add. heat
Mixed add. heat
Only additional heat
Comp. + add. heat
Only compressor
Chapter 5.6.25,
No, Yes
00:00 - 23:59
6 720 645 172 (2010/07) en
HP
E21
E21
E21
E21