inch gap between
bolt and rotor.
Bump the thru
bolt with
a lead mallet
to break the rotor
loose (4.5, 5.5, 7, 7.5kW
only)
for removal
(Figure 6-l 7). If the bearing turns freely
and has no sign of damage do not remove, the fan will be
removed with rotor
(Figure 6-18).
NOTE
On 7.5kW,
if the rotor
seems loose but can not
be removed,
see Section 6-3.2.
Figure 6-16.
Stator
Figure 6-17.
Rotor Thru Bolt
15.2.
Two-Pole
Removal
(3.5kW).
On the 3.5kW, the rotor
is held to the engine crankshaft
by right-hand
threads on
the crankshaft
and in the rotor
shaft (engine rotates coun-
terclockwise
when
viewed
from
drive
side).
These
threads
have been coated with
antiseize compound
to aid disassem-
bly. To remove rotor,
place a wood block in a trailing
edge
of one rotor
pole. A sharp, medium
force hammer blow to
wood
block's
end will
free the
rotor,
allowing
it to
be
turned
off by hand (Figure 6-19).
Figure 6-18.
Removing Rotor (4.5,5.5,
7kW)
CAUTION
Do not
attempt
to remove
rotor
by blocking
engine cooling
fan and turning
rotor
with
any
kind of wrench.
Damage to fan blades and rotor
may result.
Figure 6-19.
Removing Rotor (3.5kW)
6-5