Kohler l654 Service Manual page 13

Rv generator
Hide thumbs Also See for l654:
Table of Contents

Advertisement

3. Remove
the 12 pin connector
plug it into
the tester.
from
the controller
and
NOTE
4. Observe the POL (polarity)
lamp. Green light indicates
battery
polarity
is correct.
If lamp does not light, check for
correct battery
connection
to the generator
set.
NOTE
On 5.5kW,
7kW and 7.5kW
sets the SAFETY
lamp will also be on. This indicates
the low oil
pressure switch is functioning
properly.
5. With the
IGNITION
switch
in OFF position,
press the
CRANK
button.
The CRANK
lamp should
light
and the
engine should
crank.
If the lamp does not light, no voltage
from the battery
is present.
On 5.5kW, 7kW and 7.5kW sets, the SAFETY
lamp will go off after the engine
has reached
sufficient
operating
oil pressure.
IO. To check the high temperature
cutout,
low oil pressure
cutout
and/or
the oil level cutout
for proper
operation,
start the generator
set and connect
a jumper
wire from the
cutout
device to ground.
The "amber"
safety
lamp should
light, indicating
the protective
circuit
is functioning
prop-
erly.
11. If all checks
are OK, connect
the 12 pin connector
to
the generator
set controller.
If the 15 amp fuse
blows,
check
for defective
cranking
solenoid,
fuel pump or fuel solenoid,
ignition
coil, choke
heater, fuel shutdown
control
or shorted
wiring.
6. Remove the air cleaner cover to observe the choke plate
during the next step.
If the 1 amp fuse blows, check for defective
choke
sol-
enoid
or wiring.
7. Again, with the IGNITION
switch in OFF position
press
the crank
button.
While the engine is cranking,
press the
CHOKE
button
to supply
battery
voltage
to the choke
plate
solenoid.
Make
sure the choke
plate is functioning
properly.
If not,
see Section
7. Release the CRANK
and
CHOKE
buttons.
If the 3 amp fuse blows,
check
for shorted
or grounded
generator
rotor or defective
voltage
regulator.
8. With the IGNITION
switch
ON, start the engine,
using
CRANK
and CHOKE
buttons
as needed.
If engine does not
start, see Engine
Troubleshooting,
Table 4-l. With engine
at operating
speed, press V.B.U. (voltage
build-up)
button
momentarily.
Check
for generator
output
voltage.
If no
output
voltage
is available,
see Troubleshooting
Gen-
erator., Table 4-2.
9. Turn the IGNITION
switch
to OFF position
to stop the
engine.
4-3.
TROUBLESHOOTING
Refer
to Table 4-l
for engine troubleshooting.
To make
engine
repairs,
refer to the Kohler
engine service manual
which
covers the engine
model.
A troubleshooting
chart
cannot
cover every
possible cause of malfunction.
Always
consider
every
possible cause of malfunction.
Knowledge
of
four
cycle
engines
and
battery
ignition
systems
can
be applied.
Refer to Table 4-2 to troubleshoot
the genera-
tor. The table refers to applicable
paragraphs in the manual.
4-2