3-6 Using Memory Cards
@ Manual Transfer
Use screen operations to select the direction (download, upload), contents (project, project
and system, or system), and banks.
Set pin 6 of the DIP switch to ON for manual transfer.
1
OFF
Use the following procedure to manually transfer data.
1. Turn OFF the power to the PT.
2. Turn ON pin 6 of the DIP switch.
3. Insert the Memory Card into the PT.
4. Turn ON the power.
5. The following screen will be displayed on the PT.
6. Specify the direction, contents (project, project and system, or system), and bank.
7. The IPP file name and system version that are stored in both the specified bank of the
Memory Card and the PT will be displayed in the Project File and System Version fields.
After confirming the details, press the Go Button.
8. A message confirming the transfer will be displayed. Press the OK Button to execute the
specified data transfer operation. When downloading, the screen data previously stored in
the PT will be deleted.
9. A warning message will be displayed if the PT model, system program/screen data ver-
sions, and language for the data stored in the PT are different from that for the data
stored in the Memory Card. Press the Yes Button to continue transferring the data.
10. The uploading/downloading screen will be displayed while data is being transferred. A
screen indicating that the transfer has completed will be displayed when the transfer has
finished. (If an error occurs, a transfer error screen will be displayed. Refer to page 3-25 if
an error occurs.)
11. The indicator will flash green when transferring has finished.
12. Turn OFF pin 6 of the DIP switch and reset the PT.
A warning message is not displayed at the PT when the PT model, version, and language are
different if the system programs used are version 1.0@.
Therefore, if the wrong data is downloaded, execute the transfer operation again using auto-
matic download.
The system settings cannot be changed for the upload operation.
3-24
DIP switch pin and status
2
3
4
OFF
OFF
OFF
OFF
5
6
7
8
ON
OFF
OFF
Operation
Manually downloads or uploads
system programs and screen data.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ns7-sv00Ns7-sv01Ns12-ts01Ns10-tv00Ns10-tv01Ns12-ts01 series ... Show all

Table of Contents