Advertisement

5-1 Connecting to Host Via Ethernet
tions Unit mounted at a node. If there is more than one Communications Unit at a node, each
Unit will contain a local network table.
Remote Network Table
The remote network table provides the node and network address corresponding to the initial
relay point (first point the data must pass) en route to a target network (end network) not di-
rectly connected to the local PLC. The table specifies the route from the relay point to the end
network.
PT at local
node
Routing tables are created using the CX-Programmer and then transferred to the host. Refer
to the CX-Programmer User Manual for actual procedures.
The methods for setting each Unit are described next.
· CS-series PLCs
Note
CS1G/CS1H and CS1G/CS1H-H Ethernet Units:
Setting the Front Panel Switches
Setting Unit Numbers
Always set the unit numbers so that the unit numbers of other CPU Bus Units mounted to the
5-8
Unit number 04
Unit number 02
Local network
address
Network 2
Network 3
Node 1
Node 2
Network 1
Remote Network Table for Local PT
Destination
Relay
Gateway
network
network
node
address
addreww
address
Meaning: To go to network 3,
first go to node 3 of network 1.
· Always turn OFF the power to the PLC before setting the rotary switches.
· Create I/O tables for the CPU Unit when setting the unit number for the first time or chang-
ing settings.
CS1W-ETN01
CS1W-ETN11
Local network table
Unit number
Node 3
Relay PLC
Relay PLC
(a)
(b)
Network 2
Remote Network Table for PLC (a)
Destination
Relay
Gateway
network
network
node
address
addreww
address
Meaning: To go to network 3,
first go to node 2 of network 2.
Node 2
Desti-
Node 2
Node 2
nation
Network 3
Local Network Table for PLC (b)
Local
Unit
network
number
address