Solution 6000
Installation Manual
Inputs > Commands >

Smoke Sensor Reset

This command allows you to reset smoke sensors.
When initiated this command will cause any outputs
programmed as Event Type 49 — Smoke Sensor GND in
the chosen area to turn off for 10 seconds.
1) Enter [MENU] + [3] + [0] + [5] and use the up and
down arrows to highlight the area that you want to
reset the smoke detectors in then press [OK].
Smoke Detector reset in
progress. Please wait
2) The keypad will automatically return to the menu
when all smoke detectors in the area has been
reset.
Smoke detectors must have the negative power
i
terminal connected to an output programmed as
Note
Event Type 49 for this command to work.
ZO N E D E FAU LT TA B L E
The table below lists the default values for all zone parameters in the control panel. Zones marked as Not Used do not
require EOL resistors to be fitted.
Programming

Zone Name

Zone Type

Area Assignment
Pulse Count
Pulse Count Time
Door Assignment
Report Route
Reporting Options
Lockout Dialler
Report Alarm
Report Troubles
Report Bypass
Reserved
Reserved
Report Restores
Delay Reporting
Zone Options
Lockout Siren
Silent Alarm
Inverted Seal
Bypass Allowed
Sensor Watch
Armed In Part On
No EOL Required
Test On Exit
7-4
Input Programming
-
-
MENU 3-0-5
Zone 1
Zone 2
Zone 1
Zone 2
1 = Delay 1
5 = Handover
1
1
0
0
120
120
0
0
2
2
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
N
Y
Y
N
N
Y
Y
N
N
N
N
Y
Y
N
N
Y
Y
N
N
N
Y
Table 21: Zone Defaults
ZO N E P R O P E R T I E S
Inputs > Zone Properties >
Zone Name
Z o n e
1
N a m e
This menu allows you to program the name for each zone.
Zone names can be up to 20 characters long.
1) Enter [MENU] + [3] + [1] + [0] and use the up and
down arrows to highlight the Zone in the list then
press [OK]. Alternatively, you can enter the zone
number directly and press [OK].
2) User the arrow and number keys to move and
change text. When the Zone Name is complete,
press [OK]. At any time you can press the [OFF] key
to clear the text from the current cursor position to
the end of the line.
Zone Name Zn1
Zone 1 Name
Press  OK to SAVE
See Alpha Text Programming in Section 4 -
i
Programming Overview for further detail on entering
Note
alpha text.
Zone 3
Zone 4
Zone 3
Zone 4
5 = Handover
5 = Handover
1
1
0
0
120
120
0
0
2
2
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
N
Y
Y
N
N
Y
Y
N
N
N
N
Y
Y
N
N
Y
Y
N
N
Y
Y
-
MENU 3-1-0
Zones 5 - 16
Zones 17 - 144
Zone 5 to 16
Zone 17 to 144
3 = Instant
0 = Not Used
1
1
0
0
120
120
0
0
2
2
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
N
Y
Y
N
N
Y
Y
N
N
N
N
Y
Y
N
N
Y
Y
N
N
Y
Y
Bosch Security Systems 07/14 BLCC610I

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents