2) Use the up and down arrow keys to select the Event
Type required then press [OK] to save and exit or
press [MENU] to exit without saving. It is also
possible to directly enter the Event Type number
then press [OK].
Event Type Op1
36 - External Audible
Press  0-9 OK to Save

01 - Battery Trouble

This event type will cause the output to operate when
the panel detects a low or missing stand-by battery
and will reset once a successful battery test has been
performed.
Battery tests are performed automatically every 4 hours
and when the system is armed. A manual test can also be
requested at any time while the system is disarmed. See
MENU 7-9-1 — Battery Test
02 – AC Trouble
This event type will cause the output to operate when
the panel detects that the AC mains power has been
missing for 1 minute and will reset when the power has
been restored for 1 minute.
03 – Telco Line Fail
This event type will cause the output to operate
when the panel detects that the telco line has been
disconnected for 30 seconds and will reset when the line
has been restored.
04 – Comm Fail
This event type will cause the output to operate if the
panel fails to report to destination1 or 2 or both. The
panel will try to send the report as many times as set in
the call attempt counter before registering a comm fail.
The output will restore as soon as a successful report has
been sent to the destination that has previously failed to
report. If both Destination 1 and Destination 2 had failed
to report then successful report to both destinations will
need to be made before the output will reset. See MENU
5-2-0 — Call Attempt Count
05 – 3rd Dial Attempt
This event type will cause the output to operate when
the panel has made 3 unsuccessful call attempts to the
base station. The output will reset when all pending
messages have been sent or when the maximum number
of call attempts have been made.
06 – Dest Reporting
This event type will cause the output to operate
when the panel is communicating via Destination 1,
Destination 2 or Destination 3 (Email) and will reset when
the transmission ends.
8-4
Output Programming
07 – Reserved
08 – Dest Kiss Off
This event type will cause the output to operate when
the panel receives an kiss-off acknowledgment from the
receiving party while communicating via destination 1
or 2. It is recommended that this output is programmed
with a one-shot timer.
09 – User Keyfob Func 1
This event type will cause the output to operate when
Key X is pressed on the Keyfob. This output type is user
specific and requires a 4 button keyfob.
i
In previous versions, programming an output with
event type 09 - Keyfob Function 1 to follow the keyfob
Note
for user 255 would cause the control panel to restart.
This is only an issue for user 255. In version 2.14, this
has been corrected.
10 – User Keyfob Func 2
This event type will cause the output to operate when
Key Y is pressed on the Keyfob. This output type is user
specific and requires a 4 button keyfob.
i
In previous versions, programming an output with
event type 10 - Keyfob Function 2 to follow the keyfob
Note
for user 255 would cause the control panel to restart.
This is only an issue for user 255. In version 2.14, this
has been corrected.
11 – Dialler Disabled
This event type will cause the output to operate if the
panel reporting functions are manually disabled and
will reset when reporting is enabled. See MENU 5-2-1 —
Dialer Options.
12 – Output Device Missing
This event type will cause the output to operate when
the panel detects that a horn speaker is missing. The
output will reset when the horn speaker is reconnected.
Only output 1 and 2 can be programmed as a horn
speaker outputs. See MENU 4-1-3 — Output Polarity for
information on configuring an output to drive a horn
speaker
13 – Output Trouble
This event type will cause the output to operate when
the panel detects that an output device is missing or in
an overload condition. The output will reset when all
failed outputs have restored or the overload condition
has been removed.
14 – Panel On Line
This event type will cause the output to operate when
the panel seizes the phone line and will reset when the
phone line is released.
Bosch Security Systems 07/14 BLCC610I