4.4 Commissioning Record Tables

These tables should be completed during commissioning as a record of the commissioning tests.
Relay Type
Substation
Tester
4.4.1 Secondary Injection Tests
4.4.1.1 Overcurrent
IDMTL/DTL Characteristic
Table 4-4
Pick-up/Drop-off Results
Pole
Pick-up setting
Phase A
Phase B
Phase C
E/F
Table 4-5
Timing Characteristic Results
Characteristic
Pole
(NI, VI, EI,
LTI, DTL)
Phase A
Phase B
Phase C
E/F
Lowset and Highsets
Table 4-6
Lowset setting results
Pole
Lowset setting
Phase A
Phase B
Phase C
E/F
©2013 Siemens Protection Devices Limited
Serial Number
Feeder Identity
Date
Pick-up error
Measured pick-up
( 4% of 105%)
2x Is
Error
Delay
( 5% or
Delay
30 ms)
Measured pick-up
7SG11 Argus User Manual
Measured
drop-off
5x Is
Error
( 5% or
30 ms)
( 5% of setting)
Drop-off error
( 95% of pick-up)
Error