Page 1
Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
Page 2
7SG163 Ohmega 300 Series SingleDEF Contents 1 Introduction............................3 2 DEF Direction and Characteristic Angle..................3 DEF Schemes ........................... 4 2.1.1 DEF Direct Trip ......................... 4 2.1.2 DEF POR .......................... 4 2.1.2.1 Current Reversal Guard ....................4 2.1.2.2 CB Echo ........................
Page 3
7SG163 Ohmega 300 Series SingleDEF 1 Introduction. High resistance earth faults present difficulties to impedance measuring elements since resistive coverage required can often extend beyond the apparent impedance presented by maximum load conditions. In those cases a directional earth fault element can be used to supplement the basic distance protection.
Page 4
7SG163 Ohmega 300 Series SingleDEF 2.1 DEF Schemes There are two active schemes for the relay. 2.1.1 DEF Direct Trip In the DEF Direct Trip mode, the relay will trip on detecting an earth fault in the set direction. The DEF element is time graded, and may be set to standard IEC or ANSI Curves or as a DTL element.
Page 5
7SG163 Ohmega 300 Series SingleDEF 3 Relay Settings 3.1 DEF Auxiliary Protection S ttings. DEF Protection - Allows the DEF Element to be enabled or disabled DEF Active Scheme - Active scheme may be set as either DEF POR or DEF Direct trip. For more details on these schemes see part 2.1 of this section.