Siemens 7SG11 Manual page 183

Hide thumbs Also See for 7SG11:
Table of Contents

Advertisement

FUN
INF
Description
164
118
SEF Instantaneous
164
119
Hot line working
164
129
Reset Energy Meters
164
130
Reset Maximum Demand
255
0
Initiate General Interrogation
255
0
Time Synchronisation
Note: Events listing a GI cause of transmission can be raised and cleared; other events are raised only.
3.2 Modbus RTU Definitions
The following tables give information on the IEC 60870-5-103 protocol. A detailed description of all
protocol information is available in report no 434/TM/5/13 which can be accessed on the
protection.com
in publications section under technical reports, "communications interface manual".
The tables below detail the MODBUS address map, listing data points that are available and the
functions supported for access. Please note, not all addresses will apply to all models.
To configure MODBUS a new setting has been added to the communications sub-menu to select the
protocol to use, either IEC60870-5-103 or MODBUS-RTU. After selecting MODBUS, set the remaining
parameters, baud rate, parity, station (slave) address, line idle and data echo as appropriate.
When an electrical RS485 module is connected to the Argus relay, the Line Idle and Data Echo
settings must both be set to OFF.
Table showing Coil Addresses
MODBUS
IEC
IEC
Address
FUN
INF
00016
160
16
00019
160
19
00023
160
23
00024
160
24
00025
160
25
00026
160
26
01059
164
35
01060
164
36
01061
164
37
01062
164
38
01075
164
51
01076
164
52
01077
164
53
©2010 Siemens Protection Devices Limited
COM
ON/OFF
ON/OFF
ON/OFF
ON/OFF
-
-
Description
Autoreclose
Reset Flag & Outputs *
Settings Group 1 Select
Settings Group 2 Select
Settings Group 3 Select
Settings Group 4 Select
Settings Group 5 Select
Settings Group 6 Select
Settings Group 7 Select
Settings Group 8 Select
Energise Output 1
Energise Output 2
Energise Output 3
7SG11 Argus 2 Diagrams and Parameters
TYP
COT
20
20
20
20
20
20
20
20
7
9
6
8
COM
ON/OFF
ON
x
x
ON
x
x
ON
x
x
ON
x
x
ON
x
x
ON
x
x
ON
x
x
ON
x
x
ON
x
x
ON
x
x
ON
x
x
ON
x
x
x
x
x
-
x
x
x
x
www.reyrolle-
P20009 Page 24 of 37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sg11Argus 7sg116

Table of Contents