Mantel And Wall Projections - Majestic MDVI30IN Installation Manual

Ruby series
Hide thumbs Also See for MDVI30IN:
Table of Contents

Advertisement

1-1/2 IN.
SURROUND
A
Alternate Unit Width
D
B
Alternate Unit Depth
D
C
Alternate Unit Height
D
Note: Dimensions assume 1/4 inch clearance on all sides.
Note: If exhaust collar on insert and fi replace damper do not line up, add 4 inches (102 mm) to minimum
fi replace height for bends in vent pipe.
Figure 4.3 Firebox Opening - Deep Surround
B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Clearance to combustible material under the insert is 1/4
inch (6 mm). Clearance from top of fi replace opening for
combustibles extending 12 inches max. is 12 inches.
• Use leveling legs to raise insert minimum 1/4 inch (6 mm)
above combustible material or outer wrap of factory built
fi rebox.
Combustible facings must not extend behind the insert
surround. For non-combustible material specifi cations
refer to Section 1.E.
10
Majestic • MDVI30IN, MDVI35IN, MDVI30IL, MDVI35IL Installation Manual • 2205-980 Rev. H • 12/16
SIDE VIEW
B
D
APPLIANCE
Location
TOP VIEW
C
D
SURROUND
MINIMUM FIREBOX OPENING
MDVI35IN/IL
Inches
Millimeters
33-1/2
851
15-1/8
384
23
584
EXISTING NON-COMBUSTIBLE FACING
Figure 4.4 Mantel Clearances
A
D
APPLIANCE
MDVI30IN/IL
Inches
Millimeters
29-1/2
14
19-3/8
12 IN. MAX.
10 IN. MIN.
749
356
492
2 IN.
MAX.
12 IN. MIN.