C. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specified. Framing closer than the minimums list-
ed must be constructed entirely of non-combustible materi-
als (i.e., steel studs, concrete board, etc.).
Note: Measurement is taken from top of the
opening, NOT the top of the fireplace.
Combustible Mantels
COMBUSTIBLE MANTEL
1/2 IN.
THICK WALL
SHEATHING
14 IN. MIN. BOTTOM OF MANTEL
TO TOP OF APPLIANCE OPENING
Figure 10.3 Clearances To Combustibles Mantels Or Other
Combustibles Above Appliance
Majestic • JADE32IN, JADE42IN, JADE42IL Installation Manual • 2491-986 Rev. K • 10/18
12 IN. MAX.
APPLIANCE OPENING
Non-combustible Mantels
1/2 IN.
THICK WALL
SHEATHING
NON-COMBUSTIBLE
NON-
COMBUSTIBLE
MANTEL
6 IN. MAX.
Figure 10.4 Clearances To Non-Combustible Mantels Or Other
Non-Combustibles Above Appliance
12 IN.MAX.
MANTEL
14 IN. MIN. BOTTOM OF MANTEL
TO TOP OF APPLIANCE OPENING
APPLIANCE OPENING
55