Siemens SINAMICS V90 Operating Instructions Manual page 95

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

No.
Name
Type
21
POS1
Level
22
POS2
Level
23
POS3
Level
24
REF
Edge
0→1
25
SREF
Edge
0→1
26
STEPF
Edge
0→1
27
STEPB
Edge
0→1
28
STEPH
Edge
0→1
Note
When working in the torque control mode, the torque setpoint equals to 0 if CWE and CCWE
are at the same status. For more information, please refer to section Direction and stop
(Page 209).
Note
Invalid circumstances for DI signals
• When SINAMICS V-ASSISTANT is communicating with the drive or you are operating the
drive on SINAMICS V-ASSISTANT, some DI signals are invalid:
– When referencing by SINAMICS V-ASSISTANT, the DI signal SREF is invalid.
– During trial run test, the DI signal SON is invalid; meanwhile, DI7 and DI8 are
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884
Description
Select position setpoint.
A combination of the signals POS1 to POS3 can se-
lect eight fixed position setpoint sources.
POS3 : POS2 : POS1
0 : 0 : 0: fixed position setpoint 1
0 : 0 : 1: fixed position setpoint 2
0 : 1 : 0: fixed position setpoint 3
0 : 1 : 1: fixed position setpoint 4
1 : 0 : 0: fixed position setpoint 5
1 : 0 : 1: fixed position setpoint 6
1 : 1 : 0: fixed position setpoint 7
1 : 1 : 1: fixed position setpoint 8
Set reference point with digital input or reference cam
input for reference approaching mode.
0→1: reference input
The reference approach will be started with the signal
SREF.
0→1 start reference approach
Step forward to the next fixed position setpoint.
0→1 start step action
Step backward to the previous fixed position setpoint.
0→1 start step action
Step to the fixed position setpoint 1.
0→1 start step action
occupied by SINAMICS V-ASSISTANT.
Connecting
4.3 Control/Status interface
Control mode
PTI
IPos
S
X
X
X
X
X
X
X
X
X
X
X
X
T
X
X
X
X
X
X
95

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics s-1fl6

Table of Contents