Siemens SINAMICS V90 Operating Instructions Manual page 295

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

Par. No.
Name
p29033
PTO: Direction change
Description: Select the PTO direction.
0: PTO positive
PTO direction does not change. PTO A leads PTO B with 90 degrees when the motor rotates in clockwise
direction. PTO B leads PTO A with 90 degrees when the motor rotates in counter- clockwise direction.
1: PTO negative
PTO direction changes. PTO A leads PTO B with 90 degrees when the motor rotates in counter-clockwise
direction. PTO B leads PTO A with 90 degrees when the motor rotates in clockwise direction.
p29035
VIBSUP activation
Description: Select the VIBSUP on/off.
Position setpoint filter can be activated (p29035) for IPos control mode.
0: Disable
Filter is not activated.
1: Enable
Filter is activated.
p29041[0..
Torque Scaling
.1]
Description:
[0]The scaling for the analog torque setpoint.
With this parameter, you can specify the torque setpoint corresponding to full analog input (10 V).
[1]The scaling for the analog torque limit.
With this parameter, you can specify the torque limit corresponding to full analog input (10 V).
You can select the internal parameters or the analog input as the source of the torque limit with the combi-
nation of the digital input signals TLIM1 and TLIM2.
Index:
[0]: Torque set scale
[1]: Torque limit scale
p29042
Offset Adjustment for
Analog input 2
Description: Offset adjustment for the analog input 2.
p29043
Fixed Torque Setpoint
Description: Fixed torque setpoint.
You can select the internal parameters or the analog input as the source of the torque setpoint by configuring
the digital input signal TSET.
p29050[0..
Torque limit upper
.2]
Description: Positive torque limit.
Three internal torque limits in total are available.
You can select the internal parameters or the analog input as the source of the torque limit with the combina-
tion of the digital input signals TLIM1 and TLIM2.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884
Min
Max
0
1
0
1
0
[0] 100
[1] 300
-0.50
0.50
-100
100
-150
300
Factory
Unit
Data
Setting
type
0
-
I16
0
-
I16
[0] 100
%
Float
[1] 300
0.00
V
Float
0
%
Float
300
%
Float
Parameters
10.2 Parameter list
Effective
Can be
changed
IM
T
IM
T
IM
T
IM
T
IM
U, T
IM
T
295