4.3.2.2

PTOs

High-speed 5 V differential signals (A+/A-, B+/B-, Z+/Z-) and open collector (zero pulse) are
supported.
Wirings
When not using the open collector:
4.3.3

Analog inputs/outputs (AIs/AOs)

4.3.3.1

AIs

SINAMICS V90 has two analog input terminals. The input voltage at each analog input
varies with control modes.
Pin No.
19, 20
21, 22
* If the AI input voltage is higher than 10 V, the speed is not limited to the value at 10 V (p29060), but
scaled according to p29060. For example, if p29060 = 3000 rpm, the speed is 3300 rpm at 11 V and
3600 rpm at 12 V.
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 09/2015, A5E36037884
Analog input
Input voltage
Analog input 1
0 V to 10 V
0 V to 10 V
-10 V to +10 V
0 V to 10 V
Analog input 2
0 V to 10 V
0 V to 10 V
0 V to 10 V
-10 V to +10 V
When using the open collector:
Control mode
PTI
IPos
S
T
PTI
IPos
S
T
Connecting
4.3 Control/Status interface
Function
Not used
Not used
Speed setpoint (reference
p29060) *
Speed limit (reference p29060) *
Torque limit (reference r0333)
Torque limit (reference r0333)
Torque limit (reference r0333)
Torque setpoint (reference r0333)