COMBIMASTER & MICROMASTER Integrated
REFERENCE MANUAL
Parameter
Function
P092 • • • •
Serial link baud rate
P093 • • • •
Serial link timeout
(seconds)
P094 • • • •
Serial link nominal
system setpoint (Hz)
P095 • • • •
USS compatibility
P099 • • • •
Communication
adapter type
P101 • • • •
Operation for Europe
or USA
P111
Inverter power rating
(kW/hp)
P112
Inverter type
P113
COMBIMASTER / MMI
model
P121
Enable/disable RUN
button
Siemens plc. 1999
©
| G85139-H1731-U300-D2
Range
[Default]
3 – 7
Sets the baud rate of the RS485 serial interface (USS
protocol):
[6]
3 = 1200 baud
4 = 2400 baud
5 = 4800 baud
6 = 9600 baud
7 = 19200 baud
Some RS232 to RS485 converters are not capable of baud
rates higher than 4800.
0 - 240
This is the maximum permissible period between two
incoming data telegrams. This feature is used to turn off the
[0]
inverter in the event of a communications failure.
Timing starts after a valid data telegram has been received
and if a further data telegram is not received within the
specified time period, the inverter will trip and display fault
code F008.
Setting the value to zero switches off the control.
Setpoints are transmitted to the inverter via the serial link as
0 -
percentages. The value entered in this parameter
fmax**
represents 100% (HSW = 4000H). – refer to USS reference
[50.00]
document (see Section 5.7)
0 = Compatible with 0.1 Hz resolution
0 - 2
1 = Enable 0.01 Hz resolution
[0]
2 = HSW is not scaled but represents the actual
frequency value to a resolution of 0.01 Hz
5000 = 50 Hz).
Note : Unit will only output 0.05Hz resolution
0 = Option module not present
0 - 2
1 = PROFIBUS module (enables parameters relating
[0]
to PROFIBUS)
2 =
CANBUS (SW Version : 3.00 onwards)
This changes the power display between kW and HP:
0 - 1
[0]
0 = Europe (kW)
1 = USA (HP)
Read-only parameter that indicates the power rating of the
0.0-10.00
inverter in kW. e.g. 0.55 = 550 W
[!!!]
If P101 = 1 then the rating is displayed in hp.
Read-only parameter.
1 - 8
1 = MICROMASTER series 2 (MM2)
[8]
2 = COMBIMASTER
3 = MIDIMASTER
4 = MICROMASTER Junior (MMJ)
5 = MICROMASTER series 3 (MM3)
6 = MICROMASTER Vector (MMV)
7 = MIDIMASTER Vector (MDV)
8 = COMBIMASTER/MMI series 2
10-29
Read only parameter
[-]
10 = CM12(/2)
11 = CM25(/2)
12 = CM37(/2)
13 = CM55(/2)
14 = CM75(/2)
0 = RUN button disabled.
0 - 1
1 = RUN button enabled (only possible if
[1]
P007=1).
Description / Notes
20 = CM37/3
25 = CM220/3
21 = CM55/3
26 = CM300/3
22 = CM75/3
27 = CM400/3
23 = CM110/3
28 = CM550/3
24 = CM150/3
29 = CM750/3
(e.g.
33