Parameter
P031 • • • •
Jog frequency right
(Hz)
P032 • • • •
Jog frequency left
(Hz)
P033
Jog ramp up time
(seconds)
(SW Version : 3.00
onwards)
P034
Jog ramp down time
(seconds)
(SW Version : 3.00
onwards)
P035
Reverse motor
direction
P041 • • • •
Fixed frequency 1
(Hz)
P042 • • • •
Fixed frequency 2
(Hz)
P043 • • • •
Fixed frequency 3
(Hz)
P044 • • • •
Fixed frequency 4
(Hz)
P045
Inversion fixed
setpoints for
fixed frequencies
1 - 4
P046 • • • •
Fixed frequency 5
(Hz)
P047 • • • •
Fixed frequency 6
(Hz)
26
Function
Range
[Default]
0 - fmax**
[5.00]
0 - fmax**
[5.00]
0.00 –
650.00
[10]
0.00 –
650.00
[10]
0 – 1
[0]
0 - fmax**
[5.00]
0 - fmax**
[10.00]
0 - fmax**
[15.00]
0 - fmax**
[20.00]
0 - 7
[0]
0 - fmax**
[25.00]
0 - fmax**
[30.00]
COMBIMASTER & MICROMASTER Integrated
Description / Notes
Jogging is used to advance the motor by small amounts. It is
controlled via the JOG button or with a non-latching switch
on one of the digital inputs (P051 to P053).
If jog right is enabled (DINn=7), this parameter controls the
frequency at which the inverter will run when the switch is
closed. Unlike other setpoints , it can be set lower than the
minimum frequency.
If jog left is enabled (DINn=8), this parameter controls the
frequency at which the inverter will run when the switch is
closed. Unlike other setpoints , it can be set lower than the
minimum frequency.
This is the time taken to accelerate from 0Hz to maximum
frequency (P013) for jog functions. It is not the time taken to
accelerate from 0Hz to the jog frequency. If DINn =16 (see
P051 to P053) then this parameter can be used to override th
normal Ramp-up time set by P002.
This is the time taken to decelerate from maximum frequency
0Hz to (P013) for jog functions. It is not the time taken to
decelerate from the jog frequency to 0Hz. If DINn =16 (see
P051 to P053) then this parameter can be used to override th
normal Ramp-down time set by P003.
0 = Normal direction control.
1 = Direction control is reversed.
Valid if
P006 = 2 and P053 = 6 or 18
or
P051 = P052 = P053 = 17.
Valid if
P006 = 2 and P052 = 6 or 18
or
P051 = P052 = P053 = 17.
Valid if
P006 = 2 and P051 = 6 or 18
or
P051 = P052 = P053 = 17.
Valid if
P006 = 2 and P051 = P052 = P053 = 17.
Sets the direction of rotation for the fixed frequency.
FF1
P045 = 0
P045 = 1
P045 = 2
P045 = 3
P045 = 4
P045 = 5
P045 = 6
P045 = 7
⇒ Fixed setpoints not inverted.
⇐ Fixed setpoints inverted.
Valid if P006 = 2 and P051 = P052 = P053 = 17.
Valid if P006 = 2 and P051 = P052 = P053 = 17.
Siemens plc. 1999
©
REFERENCE MANUAL
FF2
FF3
FF4
| G85139-H1731-U300-D2