Summary of LonMark Objects, Variables, and Configuration Properties
All of the network variables and configuration properties are listed in this table�
Items marked in green in the UFPT are inherited from the SFPT�
 
Func 
LonMark 
Network 
tional 
Configuration 
Variable 
Block 
Property 
co2Sensor 
  
SCPTmaxSendTime 
  
SCPTminSendTime 
 nvoCO2Ppm 
(principal) 
 
  
SCPTminDeltaCO2 
  
  
nviCO2SetPtPpm 
  
 
nvoCO2SetPtPpm 
nvoCO2Percent 
  
SCPTminDeltaRH 
nvoIAQGood 
nvoCO2Fault 
hvacTempSensor 
  
SCPTmaxSendTime 
  
SCPTminSendTime 
 nvoHVACTemp 
(principal) 
 
  
SCPTminDeltaTemp  SNVT_temp_p
nviTempSetPt 
nvoTempSetPt 
nvoTempFault 
hvacRelativeHumiditySensor 
  
SCPTmaxSendTime 
  
SCPTminSendTime 
 nvoHVACRH 
(principal) 
 
  
  
  
SCPTminDeltaRH 
nvi_rH_SetPt 
nvo_rH_SetPt 
nvo_rH_Fault 
occupancySensor 
SCPTmaxSendTime 
nvoOccup 
(principal) 
 
nvosOccup 
 
nviDriveOccIcon 
  
nvisDriveOccIcon 
  
relayOutput 
nviRelayDrive 
  
 
(principal) 
Node 
nviRequest 
  
  
nvoFileDirectory 
  
  
nvoStatus 
  
Virtual Functional Block 
nvoChkSum 
  
 
nvoHeartBeat 
 
 
72
Root 
Self‐Documentation 
Data Type 
String 
SFPTco2Sensor (1070)
SNVT_time_sec
SNVT_time_sec
SNVT_ppm 
 
SNVT_ppm
SNVT_ppm 
 
SNVT_ppm
SNVT_lev_percent percent of 2000 ppm
SNVT_lev_percent
SNVT_switch
if(no fault and conc < sp) On, else Off
SNVT_switch
if (gas sensor fault) On, else Off
SFPThvacTempSensor(1040)
SNVT_time_sec
(standard)
SNVT_time_sec
(standard)
SNVT_temp_p 
 
SNVT_temp_p
SNVT_temp_p
SNVT_switch
if(sensor fault) On, else Off
SFPThvacRelativeHumiditySensor(1050)
SNVT_time_sec
SNVT_time_sec
SNVT_lev_percent   
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_switch
if(sensor fault) On, else Off
SFPToccupancySensor
SNVT_time_sec
(standard)
if(Internal timer running) OC_OCCUPIED, 
SNVT_occupancy 
else OC_UNOCCUPIED. 
SNVT_switch
if(Internal timer running) On, else Off
if(OC_OCCUPIED) force white stick man 
SNVT_occupancy 
to appear at top of LCD 
if(On) force white stick man to appear at 
SNVT_switch 
top of LCD 
SFPTopenLoopActuator
Ignored unless set in Config/Outputs/Rly 
SNVT_switch 
Src. 
SFPTnodeObject
SNVT_obj_request
SNVT_address
SNVT_obj_status
SNVT_count
Counts every 2 seconds to confirm 
SNVT_count 
communication. 
Default 
Min 
Max 
 
300 
2  
300
seconds 
5.0 
2  
300
5000 
   0 (CO2) 
(CO2) 
 
450 (VOC) 
2000 
(VOC) 
10 
5000
equivalent 
5000 
400 (CO2) 
(CO2) 
 
605 (VOC) 
1999 
(VOC) 
850 
 
0.0 
100.0
percent of 
1
0.0 
100.0
2000 ppm 
 
 
300 
300
seconds 
5
300
50 
 
on wire, 
0.3 
50
translated by 
10, can  
30, can 
LonMaker 
68 
config. 
config 
 
300 
300
seconds 
5
300
 
1
100 
50 
 
300 
300
seconds
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
10000 
 
unit 
 
ppm or 
 
bit 
Celsius 
bit
percent 
bit
bit 
bit 