Honeywell IAQPoint2 User Manual page 49

Air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

Available languages

Available languages

Simulate
Simulate
Normal
Max
Min
Gas
Temp
rH
Rly
Simulated output permits creating high or low outputs on the three sensors, allowing the operator
to verify that the system will respond as planned to changes in the gas level, temperature, or
humidity level� Any combination of minimum, maximum, or normal values of gas, temperature, and
humidty can be simulated� Default simulation selections are normal for all three parameters�
Additionally, the relay can be forced on or off from this screen� This can be useful to confirm
the operation of external equipment� For example, a service person can simulate a high CO
concentration to confirm that an external fresh air damper moves to the full open position�
None of the monitor's configured values is affected by changes in the Simulate menu�
Language
Language / Langage
English
Français
The IAQPoint2 monitor can be configured for English or French (Français)� The default language
selection is English�
IAQPoint2™
2
43

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E3point

Table of Contents