Available languages

Available languages

IAQPoint2™
Property
object_identifier
object_type
enumerated
event_state
enumerated
object_name
character string
out_of_service
boolean
present_value
real
reliability
enumerated
status_flags
in_alarm
boolean
fault
boolean
overridden
boolean
out_of_service
boolean
units
enumerated
object_identifier
object_type
enumerated
event_state
enumerated
object_name
character string
out_of_service
boolean
present_value
real
reliability
enumerated
status_flags
in_alarm
boolean
fault
boolean
overridden
boolean
out_of_service
boolean
units
enumerated
object_identifier
object_type
enumerated
event_state
enumerated
object_name
character string
out_of_service
boolean
present_value
real
reliability
enumerated
status_flags
in_alarm
boolean
fault
boolean
overridden
boolean
out_of_service
boolean
units
enumerated
66
BACNet Objects and Properties
Data Type
R
C
analog_value (3)
R
C
analog_value (2)
R
R
normal (0)
R
N
"GAS_SPT_AV"
R
R
FALSE
"Gas threshold if CO2 fitted, 850 if VOC fitted, 50 (Copy of
R
N
setpoint on UI)"
O
C
no_fault_detected (0)
R
C
always false (0)
R
C
always false (0)
R
C
always false (0)
R
C
always false (0)
R
C
"if CO2 fitted, ppm (96) if VOC fitted, %
R
C
analog_value (4)
R
C
analog_value (2)
R
C
normal (0)
R
N
"TEMP_SPT_AV"
R
C
FALSE
R
N
"20 C Copy of setpoint on UI)"
O
C
no_fault_detected (0)
R
C
always false (0)
R
C
always false (0)
R
C
always false (0)
R
C
always false (0)
R
N
"Celcisus (62) (Units here independent of UI and AI1)"
R
C
analog_value (5)
R
C
analog_value (2)
R
C
normal (0)
R
N
"RH_SPT_AV"
R
C
FALSE
R
N
"50 % rH (Copy of setpoint on UI)"
O
C
no_fault_detected (0)
R
C
always false (0)
R
C
always false (0)
R
C
always false (0)
R
C
always false (0)
R
C
percent_relative_humidity (29)
Read Value
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
"If CO2 fitted, 400 to 5000
if VOC fitted, 10 to 100"
not writable
not writable
not writable
not writable
not writable
(98)"
not writable
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
"if Celcius, 10 to 35 if Fahrenheit 50
to 95"
not writable
not writable
not writable
not writable
not writable
"Fahrenheit (64) or Celcisus (62)"
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
0 to 100%
not writable
not writable
not writable
not writable
not writable
not writable
Writable Values