IAQPoint2™
An optional calibration kit is also available� The kit contains:
• test gas
• M-502875: 0�5LPM Regulator for 58 & 103L Cylinders
• M-502585: 0�5LPM Regulator for 17L Cylinders
• M-501038: CAL GAS 17L CYLINDER NITROGEN (N2)
• M-501011: CAL GAS 103L CYLINDER NITROGEN (N2)
• M-501010: CAL GAS 103L CYLINDER 1,000 PPM CO2 BAL N2
• M-500989: CAL GAS 103L CYLINDER 2,000 PPM CO2 BAL N2
• M-512438: CALIBRATION ADAPTER IAQPOINT
• M-508808: CAL KIT TUBING 6 FEET 1/8 I�D� X 1/4 O�D�
Tools needed:
• drill
• drill bit
• #2 Phillips and 1/8 inch (3 mm) straight screwdrivers
• wire strippers
CAUTION
!
The IAQPoint2 Air Quality Monitor is not designed for industrial
applications or for use in hazardous locations�
Digital models of the IAQPoint2 monitor should be wired as indicated on the label�
Note that the meaning of the A and B symbols for EIA/RS-485 wiring varies among
vendors� Terminal 6 corresponds to BACnet '+', the Modbus 'D1' and the EIA/RS-485
'B'� Terminal 5 corresponds to BACnet '-', the Modbus 'D0', and EIA/RS-485 'A'�
DANGER
!
Line voltages may be present on the relay terminals�
12