6)* Setting is available when there is only 1 indoor unit connection and while the indoor unit operation is not operating .
7)* You can see no . 0 (no use) and no . 1 (use) while mode master indoor unit setting .
For the mode master indoor unit setting, select the no . 1 (use) . And you can release the mode master unit setting
by selecting the no . 2 (release) .
8)* Power master reset is a setting needed to supply optimized power to wired remote controller when multiple indoor units
are connected to wired remote controller in a group .
the example of installation/service mode setting
MWR-SH10N_IM_DB68-05567A-01_EN.indd 19
1 . Press the top right corner (hidden button) of the display for more than 3 seconds
and drop it . Then you can press [ + ]/[ - ] buttons and select No . 3 and press [ OK ]
button .
- Main menu will be displayed. Press [ + ]/[ - ] buttons and select No . 1 .
2 . Press [ Mode ] button to select the number you will set .
- Press [ + ]/[ - ] buttons and select No . 1 .
3 . Press [ Mode ] button to enter the data setting stage .
- When you enter the setting stage, the current setting value will be displayed .
4 . Press [ + ]/[ - ] buttons to select No . 1
- The wired remote controller option is set from both cooling and heating to
cooling only .
5 . Press the [ Fan ] button to select page No . 2 , then Press [ + ]/[ - ] buttons to select
No . 0
- The wired remote controller option is set to no use of wireless remote controller .
6 . Press the [ OK ] button to save the current settings .
- Press the [ Cancel ] button for more than three seconds to exit to normal mode
without saving settings .