Fig; Safety Precautions; Installation - Jøtul I 160 Installation And Operating Instructions Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 16

3.0 Safety precautions

3.1 Fire preventive measures
Any use of the fireplace may represent some danger. Therefore,
respect the following instructions:
• Ensure that furniture and other combustible materials do not
get too close to the fireplace.
• Let the fire die. Never extinguish it with water.
• The fireplace gets warm when used and may cause burns if
touched.
• Only remove the ashes when the stove is cold.
• Ash must be properly disposed of outdoors, or emptied where
it does not present a fire hazard.
3.2 Air supply
Warning! Please ensure that there is adequate air supply from the
outdoors to the room in which the fireplace is to be installed.
Ensure that air vents in the room where the fireplace is located
are not blocked.
An inadequate air supply could cause smoke gas to escape into
the room. This is very dangerous! Symptoms of this include smoky
smell, drowsiness, nausea and feeling ill.
Avoid using mechanical fan vents in a room with a fireplace.
This may cause negative pressure and draw poisonous gasses
into the room.

4.0 Installation

4.1 Floor
Foundations
Ensure that the floor is strong enough for the fireplace. See «2.0
Technical data» for weights.
Combustible floor protection
If the fireplace is to be mounted on a combustible floor, cover
the floor under and in front of the fireplace with a plate made
of metal or other non-combustible material. The recommended
minimum thickness is 0,9 mm.
Any flooring made of combustible material, such as linoleum,
carpets, etc. must be removed from under the floor plate.
Requirement for protecting combustible
flooring in front of fireplace
The front plate must be in accordance with national laws and
regulations.
Contact your local building authorities regarding restrictions and
installation requirements.
4.2 Wall
Distance to walls protected by a firewall -
see fig. 1
Firewall requirement
The firewall must be at least 100 mm thick and be made of
brick, concrete-stone or light concrete. Other materials and
constructions with satisfactory documentation may also be
used.
Contact your local building authorities regarding restrictions and
installation requirements.
Min. distance from heat shield to a firewall: 15 mm.
Requirements for the stove surround
Note that the entire back panel within the surround must be
covered by firewall.
I
f the stove cowling is bricked up to the ceiling and the ceiling is
made of combustible material, on top of the warming chamber
and the cowling vents an extra ceiling panel must be installed
to avoid heating the ceiling.
For example use:
Rock wool 100 mm thick on top of a steel plate min. 0,9 mm.
Ensure airing out the top of the stove cowling – for example an
opening towards the ceiling, or approx. 5 cm
Note: Remember that it should be possible to sweep and to
inspect the installation.
Note: When the door is open, you have to secure the product to
prevent it from tipping forward, see «4.7 Set up/installation».
enGLIsH
opening (fig. 2A).
2
17

Advertisement

Table of Contents
loading

Table of Contents