Wizards
4.1 Example wizard
21. A summary of all the settings is display.
22. The final screen gives two options:
4.1.2
Basic commissioning with IOP and P0015 Macros
Basic commissioning wizard
The Basic Commissioning wizard detailed below is for Control Units with version 4.4
software or higher.
Procedure
For performing the basic commissioning of the converter with the IOP operator panel,
proceed the following steps:
1.
2.
34
If the settings are correct, select Continue.
• Save settings
• Cancel Wizard
If save is selected, a factory reset will be performed then
the settings are saved to the Inverter memory. The
location of safe data is assigned using the "Parameter
saving mode" function in "Parameter settings" in
"Menu".
Select "Basic Commissioning..." from the Wizards
menu.
Select "Yes" or "No" to a factory reset.
The factory reset is performed prior to saving all the
parameter changes that have been made during the
basic commissioning process.
Operating Instructions, 03/2013, FW V1.4, A5E00110011A4 AB
Intelligent Operator Panel (IOP)