Jog; Dol Start - ABB PST30 Installation And Commissioning Manual

Softstarters
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

Top level
Settings
Local Control
Event Log
Status Information
Reset Events
Figure 23: Jog menu
Top level
Settings
Local Control
Event Log
Status Information
Reset Events
Figure 24: DOL start menu
1SFC132003M0201

6:2.4.2 Jog

Enter the Jog menu, figure 23.
Select Jog. The motor will start and accelerate to rated speed
according to the set parameters as long as the Jog command
is activated.
Start/Stop
The motor stops immediately as soon as the command is
released.
Jog

DOL Start

6:2.4.3 DOL start
(PSTB370...1050 only)
Start from the softstarter
If required, the motor can be started DOL (Direct On Line)
with the integrated by-pass contactor.
Select the DOL start menu, figure 24.
Select DOL start to close the integrated by-pass contactor.
Start/Stop
Select Stop to open the contactor.
This menu is available only if the parameter Setting I
Jog
equal or lower than the AC-3 rating of the by-pass contactor.
DOL Start
Warning!
The rated motor current must never exceed the AC-3 rating
of the integrated by-pass contactor. See Chapter 3
"Description" for details.