1SFC132003M0201
10:56 Programmable software output V7
Path in menu:
Menu/SETTINGS/Functional Settings/
Outputs/SW Outp V7
If the softstarter is used with fieldbus communication, a fourth
output is available. This is a software output only and the
signal can be taken only through the fieldbus interface.
(See 50 "Programmable output relays, K4, K5, and K6" for
further explanations.
Parameter
Default value Setting range
text
SW Outp
Event
V7
10:57 Analog output
Path in menu:
Menu/SETTINGS/Functional Settings/
Analog Output /Analog Out
With this parameter it is possible to enable the analog output.
The softstarter has one analog output. The terminals used for
the analog output are also used for the PTC protection
though, so only one of these functions can be used at any
given time.
When sequence start is used, the analog output is only active
for the last started motor.
Parameter
Default value Setting range
text
Analog Out No
Description
Run, TOR, Event
Function of pro-
grammable soft-
ware output V7.
Description
Yes, No
Enable analog
output
Chapter 10
Functions
161