Advertisement

Chapter 10
Functions
U
70%
30%
Stop
Figure 8: End voltage for Stop ramp
U
Example 50%
100%
30%
Stop
Figure 9: Step down voltage for Stop ramp
136
10:8 End voltage
100%

10:9 Step down voltage

End voltage 30%

Time
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / End Volt
This parameter makes it possible to set the voltage level
where the stop ramp ends. The voltage or the torque will
decrease from full voltage to this level and then cut the power
to the motor. This function will be active only if parameter
Stop ramp is used.
Parameter
Default value Setting range
text
End Volt
30%
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Step Down
When stopping a motor using the stop ramp, the speed will
not decrease immediately. The step down voltage function
makes it possible to set a level where the motor speed
decreases as soon as the stop ramp begins. By this, a more
optimized stopping of the motor is achieved. This function is
not available when the stop mode is set to "torque"
Parameter
Default value Setting range Description
text
Step Down 100%
Description
30...70%
End voltage for
stop ramp
30...100%
Voltage value to
which the soft-
starter shall step
down at stop and
where it shall
commence the
stop ramp.
1SFC132003M0201
.