Step 4: Connect The Grounding Cable - Juniper MX480 Quick Manual

3d universal edge router
Hide thumbs Also See for MX480:
Table of Contents

Advertisement

MX480 3D Universal Edge Router Quick Start

Step 4: Connect the Grounding Cable

14
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
1.
the strap to an approved site ESD grounding point. See the instructions for your site.
Connect the grounding cable to a proper earth ground.
2.
Verify that a licensed electrician has attached the cable lug provided with the router
3.
to the grounding cable.
Make sure that grounding surfaces are clean and brought to a bright finish before
4.
grounding connections are made.
Attach an ESD grounding strap to your bare wrist and connect the strap to one of the
5.
ESD points on the chassis.
Place the grounding cable lug over the grounding points. The grounding point is sized
6.
for UNC 1/4-20 bolts.
Secure the grounding cable lug to the grounding points, first with the washers, then
7.
with the screws.
Verify that the grounding cabling is correct, that the grounding cable does not touch
8.
or block access to router components, and that it does not drape where people could
trip on it.
Copyright © 2015, Juniper Networks, Inc.