Connect Dryer Exhaust System

To reduce the risk of fire and combustion gas accu-
mulation the dryer MUST be exhausted to the out-
doors.
To reduce the risk of fire and the accumulation of
combustion gases, DO NOT exhaust dryer air into a
window well, gas vent, chimney or enclosed, unven-
tilated area, such as an attic, wall, ceiling, crawl
space under a building or concealed space of a
building.
This gas appliance contains or produces a chemical
or chemicals which can cause death or serious ill-
ness and which are known to the State of California
to cause cancer, birth defects, or other reproductive
harm. To reduce the risk from substances in the fuel
or from fuel combustion, make sure this appliance is
installed, operated, and maintained according to the
instructions in this manual.
To reduce the risk of fire, DO NOT use plastic or thin
foil ducting to exhaust the dryer.
To reduce the risk of fire, the exhaust duct and
weather hood MUST be fabricated of a material that
will not support combustion. Rigid or flexible metal
pipe is recommended for a clothes dryer.
Part No. 804671R2
WARNING
WARNING
WARNING
WARNING
WARNING
©
Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT
W604
1
1. Correct
2. Incorrect
W045
DO NOT use plastic, thin foil or type B ducting. Rigid metal
duct is recommended.
Locate dryer so exhaust duct is as short as possible.
Be certain old exhaust ducts are cleaned before installing your
new dryer.
Use 4 inch [102 mm] diameter rigid or flexible metal duct.
The male end of each section of duct must point away from
the dryer.
Use as few elbows as possible.
Use of duct tape or pop-rivets on all seams and joints is rec-
ommended, if allowed by local codes. DO NOT use sheet
W115
metal screws or fasteners on exhaust pipe joints which extend
into the duct and catch lint.
Ductwork that runs through unheated areas must be insulated
to help reduce condensation and lint build-up on pipe walls.
In mobile home installations, dryer exhaust duct must be se-
cured to mobile home structure.
Dryer exhaust duct MUST NOT terminate under mobile
home.
W354
Exhaust duct must not be connected to any other duct, vent, or
chimney.
Dryer exhausts 220 cfm (measured at back of dryer).
DO NOT install flexible duct in concealed spaces, such as a
wall or ceiling.
Static pressure in exhaust duct should not be greater than 0.6
inches water column [1.5 cm water column], measured with
manometer placed on exhaust duct 2 feet [610 mm] from dry-
er (check with dryer running and no load).
W048
2
SWD997N_SVG
Figure 21
Installation
19